9.4.16 MP 204 display
Line 1: Set whether the cos ϕ value is to be shown in
the MP 204 display by means of the button. See
section 7.1.3.
cos ϕ:
Enable (factory setting)
Disable.
Line 2: Set whether warnings are to be shown in the
display.
Warning:
Enable
Disable (factory setting).
If display of warnings is active, the MP 204 display
will switch from standard display (e.g. current) to
warning code display when the limit value is
exceeded. The remaining values can still be read out
by means of the button. See section 7.1.3.
9.4.17 GENIbus ID number
Set ID number.
If several units are connected to the same GENIbus,
each unit must be assigned a unique ID number.
Factory setting:
– (no number assigned).
9.4.18 Learning function
The learning function is active until the motor has
been operating for a minimum of 120 seconds. The
dot in the right side of the MP 204 display is flashing.
During the storing of the measured values, "LRN"
appears in the MP 204 display.
Three-phase operation:
Accepts the actual phase sequence as correct.
If a Pt100/Pt1000 sensor is connected, the cable
impedances to the sensor are measured.
Single-phase operation:
Starting and run capacitors are measured.
If a Pt100/Pt1000 sensor is connected, the cable
impedances to the sensor are measured.
Note: The learning function changes to "Disable"
when the measurements have been made.
Enable (factory setting)
Disable.