ZY120 6-20kVA (11) User Manual EN rev.04.doc
2. Electrical Performance
Input
Model
Voltage
Frequency
Power Factor
UPS
Single-phase
40-70Hz
>0.99(Full load)
3. Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0C-40C
<95%
<1000m
0C-70C
NOTICEIf the UPS is installed or used in a place where the altitude is above than 1000m, the
output power must be derated in use, please refer to the following:
Altitude (M)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating Power
100%
95%
91%
86%
82%
78%
74%
70%
67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion
Overload capacity
Crest ratio
1%
0.9 lag
0.1% of
normal
THD<1%
Full load
(Linear
Load)
110% load: transfers to
Bypass mode after 1 hour
130% load: transfers to
Bypass mode after 1 minute
150% load :transfers to
Bypass mode after 0.5
minute and shutdown the
output after 1 minute
3:1
maximum