14
Grounding the firewall with a grounding strip
If a grounding strip is available at the installation site, connect the grounding cable through the
grounding strip.
To connect the grounding cable:
1. Remove the grounding screw from the firewall chassis.
2. Attach the grounding screw to the ring terminal of the grounding cable.
3. Use a Phillips screwdriver to fasten the grounding screw into the grounding hole on the firewall.
4. Remove the hex nut from the grounding strip.
5. Use a needle-nose pliers to bend a hook at the other end of the grounding cable. Attach the
hook to the grounding point, and secure the hook with a screw.
Figure 11 Grounding the firewall with a grounding strip
Grounding the firewall with the grounding terminal on the rack
1. Remove the grounding screw from the firewall chassis.
2. Attach the grounding screw to the ring terminal of the grounding cable.
3. Use a Phillips screwdriver to fasten the grounding screw into the grounding hole on the firewall.
4. Remove the grounding screw from the grounding point on the rack.
5. Use a needle-nose pliers to bend a hook at the other end of the grounding cable. Attach the
hook to the grounding point, and secure the hook with the screw.
Figure 12 Grounding the firewall with the grounding terminal on the rack

Table of Contents

Other manuals for H3C SecPath F10 0 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the H3C SecPath F10 0 Series and is the answer not in the manual?

H3C SecPath F10 0 Series Specifications

General IconGeneral
BrandH3C
ModelSecPath F10 0 Series
CategoryNetwork Hardware
LanguageEnglish

Related product manuals