4
Important: With the main circuit breaker turned OFF.
Check the transformer taps at the bottom-right corner of the rear cabinet.
1-Phase Machines: The input voltage cable must be moved to the connector which corresponds to the
average voltage measured in the above step.
3-Phase Machines: The input voltage cables labeled 74, 75, and 76 must be moved to the terminal block
triple which corresponds to the average voltage measured in the above step.