11. Failure code and troubleshooting
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
AU242FHBHA Fault Code List 
Number of 
flashes by 
fault 
indicator 
Location Description 
Is it 
fixable 
1 
TE circuit of defrost 
temperature sensor, 
outdoor unit 
The detected sensor value is below 20H 
(open-circuit) or above 1000H (short-circuit) for 
60 seconds. The fault is fixable. 
Yes 
2 
TA circuit of ambient 
temperature sensor 
The detected sensor value is below 20H 
(open-circuit) or above 1000H (short-circuit) for 
60 seconds. The fault is fixable. 
Yes 
3 
TS circuit of suction 
line temperature 
sensor 
The detected sensor value is below 20H 
(open-circuit) or above 1000H (short-circuit) for 
60 seconds. The fault is fixable. 
Yes 
4 
TD circuit of 
discharge line 
temperature sensor 
After 3 minutes of compressor operation, the 
detected sensor value is below 20H 
(open-circuit) or above 1000H (short-circuit) for 
60 seconds. Fixable when below 80°C. 
Yes 
5 
TC circuit of central 
temperature sensor, 
outdoor unit 
condenser 
The detected sensor value is below 20H 
(open-circuit) or above 1000H (short-circuit) for 
60 seconds.  。 
Yes 
6 
Overcurrent  An alarm is given five seconds after the current 
limit is exceeded. Where there are 3 alarms 
within 30 minutes, the fault code is displayed. 
The fault is not fixable.   
No 
9 
IPM protection    IPM overcurrent, short-circuit, overtemperature 
and undervoltage. When the fault occurs three 
times within 30 minutes, an alarm is given and 
the fault is not fixable. 
 
10 
Base board EEPROM 
error 
857 EEPROM data access error, 11 flashes. 
The fault is not fixable. 
 
11 
Discharge line 
temperature 
protection (TD) 
After the compressor is started, the 
temperature detected by TD1 sensor is above 
120°C. The compressor is shut off in 5 seconds 
and an alarm is given. Where there are 3 
alarms within 30 minutes, the fault code 11 is 
displayed. The fault is not fixable.   
 
12 
857-to-809 
transmission error   
 
 
13 
High pressure switch 
circuit 
The high pressure switch is activated. The fault 
is corrected after the normal pressure is 
restored for 2 minutes. 
 
 
-163-