>a__WcU[S^ <[c >a`V[e[a`Wc
AU48NFIBIA malfunction code: 
Malfunction description  Code 
LED display on 
the regulating 
board 
If sent to 
indoor unit? 
Remarks 
Normal 0 Normal Yes  
Defrosting temperature 
sensor abnormal 
1 E.4. 
Yes 
Resumable 
Ambient temperature sensor 
abnormal 
2 E.1. 
Yes Resumable 
Suction temperature sensor 
abnormal 
3 E.3. 
Yes Resumable 
Discharging temperature 
sensor abnormal 
4 E.2. 
Yes Resumable 
Coil temperature sensor 
abnormal 
5 E.5. 
Yes Resumable 
O.C. 
Yes 
Over current protection  6 
P  O.C.  no 
After there are current malfunction for 3 
times in 1 hour, the testing board will 
display the last abnormal reason P X.X. 
Need powered off and restart 
Current sensor abnormal  7  C.T. 
Yes  After trouble shooting, need powered off 
and restart 
O.L. Yes 
Overload protection  8 
P  O.L.  no 
E.P. Yes 
IPM protection  9 
P  E.P.  no 
After there are current malfunction for 3 
times in 1 hour, the testing board will 
display the last abnormal reason P X.X. 
Need powered off and restart 
Read EEPROM value 
wrongly 
10  P  E.E. 
no 
Need reset and restart 
O.D. Yes 
Discharging temperature 
over high abnormal 
11 
P  O.D.  no 
After there are current malfunction for 3 
times in half an hour, the testing board 
will display the last abnormal reason P 
X.X. Need powered off and restart 
High pressure switch 
abnormal 
12 O.P. 
Yes 
Resumable 
L.U. 
Voltage over low protection  13 
P  L.U. 
Yes 
O.U. 
Voltage over high protection  14 
P  O.U. 
Yes 
After there are voltage malfunction for 3 
times in 1 hour, the testing board will 
display the last abnormal reason P X.X. 
Need powered off and restart   
Compressor overheat 
protection 
15 O.H. 
Yes 
Resumable 
Recover the parameter set 
when out of factory 
16  P  I.A. 
no 
Need reset and restart 
Clear the malfunction 
memory 
17  P  C.T. 
no  Need reset and restart 
Need reset  18  P    r.E.  no  Need reset and restart 
Radiator temperature sensor 
abnormal 
-- -- 
No use 
temporarily 
 
 
-178-