7. High pressure overhigh protection: 12 flashes of outdoor LED302 When is high pressure switch 
activated: Pressure is above 3.0 MPa.
Are connectors of CN318 pressure 
switch in good condition?
yes
yes
Check and reconnect
Is high pressure switch activated?
no
Is pressure value detected by 
pressure gage above 3MPa?
no
Replace high pressure switch
yes
yes
Are stop valves in suction 
pipe and liquid pipe of 
outdoor unit open?
no
Is piping twisted or deformed?
Open stop valve
yes
Repair or 
replacement
no
if outdoor fan motor work properly during cooling 
cycle? and if indoor fan motor and indoor EEV 
work properly during heating cycle?
Check fan motor 
or indoor EEV
yes
Is filter or heat exchanger dirty?
no
yes
cleaning
Is system overfed? Is there air in system? 
Is reading of discharging pipe pressure 
gauge oscillatory?
yes
Evacuate and recharge