Method of  the exhaust temperature control is checked with the temperature being detected   
Malfunction  by the exhaust pipe thermistor 
Detection
Be sure to turn off power switch before connect or disconnect connector,      or 
else parts damage may be occurred. 
  
    
YES
NO 
the temperature 
exceeds 110  shortly ć
after the machine 
1) The cryogen may have been leaked during 
installation, or there may be leakage in the 
piping system. 
2) There may be other causes to make the 
exhaust temperature too high.
Electrify the machine again and turn it on with 
the remote controller, then measure the 
temperature at the exhaust temperature sensor 
of the compressor on the outdoor unit 
Measure the temperature at the exhaust temperature 
sensor of the compressor on the outdoor unit
YES 
Malfunctions occur after running 
for some time? even though the   
asured temperature is below 
117ć
.
Exhaust temperature 
sensor is broken and 
needs be replaced 
NO 
HSU12/18VHJ(DB)
        Functions and control
62