7.3.10  Loop of  the station detect error
Outdoor Display
LED1  flash 18 times Indoor Display F11
LED1  flash 19 times Indoor Display F28
Method of
 
The position of the compressor rotor can not detected normally
Malfunction
 
Detection
Malfunction when the  The wiring of compressor is wrong or the connection is poor;
Decision
      or
the compressor is damaged
Conditions
Supposed
 
Ƶ
Faulty  The wiring of compressor
Causes
Ƶ
Faulty  compressor
Ƶ
Faulty  PCB
 
Troubleshooting  
* Caution
Be sure to turn off power switch before connect or disconnect connector,  
or parts damage may be occurred.
                                       Malfunction
unsolved
                               
YES
YES
NO
1. The wiring of compressor is
incorrect or the connection is
poor;
2. The compressor is damaged
IPM Module is damaged and
needs replacing.
At frist,  the compressor start up ,soon
the compressor stopped with the LED1
on the outdoor PCB blinks˄1Hz˅for 19
times
the Malfunctions exist also, .
The compressor is damaged
replace a new one
Within 3 minutes after the machine
is supplied with power and turned
on with the remote controller, the
compressor couldnot stard up