1. If the supply cord is damaged, it must be replaced by the manufacturer or its
service agent or a similar quali¿ed person. The type of connecting wire is
H05RN-F
or H07RN-F.
2. If the fuse on PC board is broken please change it with the
type of
T. 3.15A /250V.
3.Thewiringmethodshouldbeinlinewiththelocalwiringstandard.
4. After installation, the power plug should be easily reached.
5. A breaker should be incorporated into ¿xed wiring. The breaker should be
all-pole
switchandthedistancebetweenitstwocontactsshouldbenotless
than 3mm.
Outdoor unit
Install according to Drawing for the installation of indoor and
outdoor units
Tobend a pipe,givetheroundnessaslargeaspossiblenottocrushthepipe,
ƽ
andthebendingradiusshouldbe30to40
mm or longer.
Connecting the pipe of gas side ¿rst makes working easier.
ƽ
TheconnectionpipeisspecializedforR410A.ƽ
Installation of Outdoor Unit
Half union
Flare nut
Torque wrench
Becarefulthatmatters,suchaswastesofsands,etc.shallnotenterthepipe.
Thestandardpipelengthis5m.Ifitisover7m,thefunctionoftheunitwillbe
affected. If the pipe has to be lengthened, the refrigerant should be charged,
according to 20 g/m. But the charge of refrigerant must
be conducted by profes-
sional air conditioner engineer. Before adding additional refrigerant, perform air
purging from the refrigerant pipes and indoor unit using a vacuum
pump,then
Spanner
Forced fastening without careful centering may
damage the threads and cause a leakage of gas.
Pipe Diameter(Ǜ) Fastening torque
Liquid side6.35mm(1/4") 18N.m
Liquid/Gas side9.52mm(3/8") 42 N.m
Gas side 12.7mm(1/2") 55N.m
Gas side 15.88mm(5/8") 60 N.m
Connection of pipes
charge additional refrigerant.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
CAUTION
Max.Elevation: Amax=15m
Ɣ
In case the elevation A is moreƔ
than 5m, oil trap shoud be
installed every 5~7m
Max. Length: Bmax=25m
Ɣ
Incasethepipelength B isƔ
more than 10m, the refrigerant
should be charged, according
to 20 g/m.
Use the same method on indoor unit. Loosen the screws onƽ
terminal block and
insert the plugs fully into terminal block, then tighten the screws.
Insert the cable according to terminal number in the same manner as the indoor
unit.
ƽ
If wiring is not correct, proper operation can not be carried out and controller
may be damaged.
ƽ
Fix the cable with a clamp.ƽ
Connection
If the drain-elbow is used,ƽ
please attach it as ¿gure. (Note:
Onlyforheatpumpunit.)
Detach the service port’s cap of
1.
3-wayvalve,thevalverodscapfor2-wayvalve
and 3-way’s, connect the service port into the
projection of charge hose (Iow)
for gaugemanifold.
Then connect the projection of charge hose (center) for gau-
gemanifold into vacuum pump.
Open the handle at Iow in
2.
gaugemanifold, operate vacuum pump. If the scale-
moves of gause (Iow) reach vacuum condition in a moment, check 1. again.
Vacuumize for over 15min.And check the level gauge which should read -0.1MPa
3.
(76 cm Hg) at Iow
pressure side. After the
completion of vacuumizing, close the
handle ‘Lo’ in gaugemanifold and stop the operation of the vacuum pump. Check
condition of the scale and hold it for 1-2min. If the scale-moves back in spite of
tightening, make Àaring work again, the return to the beginning of 3 .
Attaching Drain-Elbow
Purging Method:To use vacuum pump
Open the valve rod for the 2-way valve to an angle of4.
anticlockwise 90 degrees.
After 6 seconds, close the
2-way valve and make the
inspection of gas leakage.
Outdoor unit A
4G0.75mm
2
3
2
^
POWER
1
)
(
N
)
(
L
)
(
C
3
2
1
)
(
N
)
(
L
)
(
C
Power cable:
HSU18VHJ(DB)
3G2.5mm
2
HSU12VHJ(DB)
2
4G0.75mm
Outdoor unit
3
2
^
POWER
1
)
(
N
)
(L
)
(
C
3
2
1
)
(
N
)
(
L
)
(
C
Indoor unit
Indoor unit
Power cable:
3G1.5mm
2
+6812/VHJ(DB)
Installations
70

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier HSU12 and is the answer not in the manual?

Haier HSU12 Specifications

General IconGeneral
BrandHaier
ModelHSU12
CategoryAir Conditioner
LanguageEnglish

Related product manuals