Part 3
4.Trouble diagnose and trouble shooting 
[46]communication between master unit connecting board and inverter board 
failure 
no
check master unit connecting board
  if connecting board
     sends serial signal to inverter board/slave
       unit PCB
no
yes
yes
        if connecting board
    receives contineous signal from inverter
board/slave unit PCB
check master unit inverter board/slave unit PCB
check power source interference
and the external noise
 
[08]indoor drainage system failure/float switch circuit on indoor PCB failure 
no
yes
if CN13 is fixed well
reconnect
if float switch works
if water pump works
check water  pump
no
no
no
no
yes
yes
yes
yes
  if C N4  is
with AC220V
 voltage
modify the wiring
and the circuit
check indoor PCB and
replace it if necessary
        if water
pump is electrified
modify the wiring
and the circuit
replace water pump
 
 
 
 
 
 
 
 
 
- 117 -