- 48 - 
2.3 Indoor checking 
No. Parts  Items  Estimation standard 
1 
Electronic 
expansio
n valve 
If the EEV has no 
response, or can not 
close fully, can not 
open 
When all indoor in cooling mode, EEV all 
open to 480 or close to min, check the 
dip switch if SW08-7 is “off”   
2 sensor 
if the coil sensor is 
inserted conversely 
or with wrong 
resistance value, 
select to test ambient 
temp. by wired 
controller or by indoor 
resistance value of indoor gas 
TC1( three cores, green), liquid pipe 
TC2 (3 cores, black) is 10KΩ ( 25) 
3 fan 
When the unit is 
running, if the voice is 
normal 
Check and resolve the problem 
4 PCB 
check if the 
communication is 
normal, and if the 
wire is connected 
reliably  
confirm indoors in one system are 
electrified accordantly, signal wire 
shielded layer of all indoor and outdoor 
units is connected together, and 
grounding on outdoor at single point 
4 Air duct  
If the flap can open 
and close normally, if 
the duct unit has air 
return duct 
Check and resolve the problem 
 
 
 
 
 
Part 2