data analysis 
No.  problem  diagnose 
1 
one EEV 
can not be 
closed fully 
open angle of EEV on stop indoor shows 4 (close 
fully), normally the coil temp. should close to indoor 
ambient temp. ( TA±3 ); this indoor two coil temp. is 
much lower than ambient temp., that is EEV does 
not closed fully and cause liquid return----to find the 
reason  
2 
sensors of 
two indoors 
are inserted 
conversely 
1.in cooling operation, the min. open angle of indoor 
EEV is 90 and the max. is 480 
2.if the sensor is inserted conversely, the EEV will 
close to min or open max. 
3.if EEV close to min, the flow volume is min too, 
temp of TC2 is low (much lower than TC1), TC1 is 
close to ambient temp; when EEV open max. the 
flow volume is too big, TC1 is low and TC2 is 
high----liquid return, please confirm if the two 
sensors are inserted properly   
3 
resistance of 
gas pipe 
sensor on 
two indoors   
is wrong 
1.  one unit does not startup, EEV open angle 
shows 4, coil temp. should be close to 
ambient temp., but TC1 shows 46, that 
should be wrong sensor resistance 
2.start one unit, EEV shows 480, but TC1 still is too 
high, that should be wrong sensor resistance   
confirm if the EEV can be open: break power supply 
and resume to listen to the EEV action voice, or turn 
off the indoor for 1 minute and turn it on to check if 
there is cooling air flow out, if yes the EEV is 
normal, if the EEV does not open please open to 
check 
check if the sensor is inserted conversely 
4 
5 indoors do 
not cool 
If all of above are normal, adjust the indoor EEV 
open angle to 90 in cooling mode   
5 
current of 
No.1 slave 
unit is 
abnormal 
position of solenoid SV4,SV5 is wrong 