Haier MRV II - 1. Working preparation before commissioning

Haier MRV II
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 26 -
Refrigerant piping length and height difference
Items Max.piping(
m)
Total piping length 250 La+Lb+Lc+LA+LB+LC+LD+LE+LF+L
G+LH+L1+L2+L3+L4+L5+L6
Actual(100)
Max. piping
length
Equivalent(
125)
LA+LB+LC+LD+ LG+LH+ L6
Max.piping length
after the first
branch
50 LG+LH+ L6
Main piping actual
length
70 LD
Height difference
between indoor
units
20 ------
Height difference
between outdoor
units
0 ------
Oil equalization pipe (L1L3)L15m L25m L35m
Balance pipe (L1'L3')L1'5m L2'5m L3'5m
Gas pipe ,liquid pipeLa+Lb5m LbLc5m LbLdLe5m Lb
Ld+Lf
Part 2
Height between indoor unit maxes at 20m
F
E
D
C
B
A
lowest indoor unit/ farthest indoor unit
L3
L2
L1
LF
L6
L5
LH
L4
LG
LE
LD
La
Lb
LB
LA
Lc
LC
50m
the first branch
50m if the indoor unit
is higer, it is 40m)
75m
MASTER
UNIT
SLAVE
UNIT
SLAVE
UNIT
SLAVE
UNIT