- 45 - 
No. Parts  Items  Estimation standard 
SV4: 2A,  4-core, yellow (from air 
discharging pipe to the top of compressor);   
SV5: 2A,  4-core, yellow ( from the top of 
compressor to air suction pipe); 
when SV4 open and SV5 close, compressor 
runs with full load, when SV4 close SV5 
open, compressor runs with half load, 
current of full load running is over than 
running with half load  
master unit SV6: 
1. two 6A valve body, 4-core, blue(at the 
balance pipe of gas-liquid separator) 
2. basic control: close during cooling, open 
during normal heating, close during oil 
equalization in heating 
1 
Solenoid 
valve 
If there is wrong 
installation of coil 
or valve body, 
electrify the unit 
and check if the 
valve body or the 
connected pipe 
is blocked, or if 
there is plenty of 
refrigerant enter 
compressor due 
to the valve body 
can not be 
closed  
master unit SV7: 2A valve body, 3-core, 
yellow wire with white terminals(oil return 
capillary of gas segregator ) 
slave unit SV7: 2A, 4-core, blue(oil return 
capillary of gas segregator) 
In operation, compressor will run; in unit 
stop, compressor will stop too. In running, 
capillary temperature behind the valve 
should be lower than ambient temp., or the 
capillary is blocked or the valve does not 
open 
 
 
 
 
 
No. Parts  Items  Estimation standard 
Part 2