factory.
Part 3
B. The indoor controlled by master/slave wired controller and the
indoor controlled by individual wired controller are all wired controlled
master indoor.
C. The remote receiver is equipped with a wire which can be
inserted in CN21.
1.3 Relative settings
1.3.1 Setting method in central control
1) Indoor central control address setting method:
Central control address dip switch: SW02 (8-bit), the setting is
below: (only the master indoor in a unit needs to be set the address)
SW02
description
[1] [2 ] [3] [4 ] [5] [6 ] [7] [8 ]
__0000000
central control address
=1
__0000001
central control address
=2
---- ----
__1111110
central control address
=1 27
__1111111
central control address
=1 28
0
set central control address by wired controller
1
Forbidden to set address by wired controller
When the first bit of SW02 is ON, indoor central control address
will be set by wired controller, and the address will be saved in
EEPROM of wired controller (it won't miss even though indoor and
wired controller are electrified again). So the first bit of SW02 must be
OFF
2) When the wired control type unit does not connect the wired
controller, the central control setting method is as follows:
In this case, you must set the PCB as remote wireless control type,