B. Indoor address setting when in central control by central controller: 
SW02 (only on the master unit). 
Part 3
           SW02   description
[1] [2] [3] [4] [5] [6] [7]         [8]
__ 0 0 0 0 0 0 0 central control address=1
__ 0 0 0 0 0 0 1 central control address=2
 ----                                     ----
__ 1 1 1 1 1 1 0 central control address=127
__ 1 1 1 1 1 1 1 central control address=128
0           
set central control address by wired controller
1                     
Forbidden to set address by wired controller
 
C. Indoor communication address 
         SW 03                                        description
[1] [2] [3] [4]          [5]          [6]          [7]           [8]
__ - 0 0 0 0 0 0 central control  address=1
__ - 0 0 0 0 0 1 central control  address=2
          ----                          ----
__ - 1 1 1 1 1 0 central control  address=63
__ - 1 1 1 1 1 1 central control  address=64
- 0                     
set central control address by wired controller
-       1                                                
Forbidden to set  address by  wired controller
0
1
set address  automatically
set address  by hand
 
There are three kinds of address setting method for indoor units: 
automatically address setting, manual address setting, wired controller 
setting. Any one of them can set the address and wired controller setting 
type has the highest priority. 
 
 
 
- 96 -