Super Match
AB09CS2ERA AB12CS2ERA AB18CS2ERA  
LED flash times
of indoor PCB
Wired 
controller 
display
Contents of 
Malfunction
Possible reasons
LED5  LED1
0
0
0
1
2
4
01
02
04
Malfunction of indoor
unit  ambient temper-
ature sensor
Sensor disconected
,or brok-
en,or at wrong position,or
short circuit 
Malfunction of indoor
unit  piping temper-
ature sensor
EEPROM wrong of
indoor PCB
EEPROM chip disconected
 
or broken  or wrong program-
med,or PCB broken 
Abnormal communi-
cation between indo-
or and outdoor units
Wrong connection,or the 
wires be disconected or wro-
ng adress setting of indoor
unit or faulty power supply 
or faulty PCB or slave unit
malfunction in MAXI system
 
 
0
0
0
0
0
7
8
12
13
14
07
/
0C
0D
0E
Abnormal communi-
cation between wired
controller and indoor  
unit
Wrong connection or  wired
controller broken,or PCB
faulty 
Malfunction of drain
system
,
Zero cross sigal 
wrong
Zero cross sigal detected 
wrong
DC Fan motor disconnected 
or DC Fan broken or circuit
broken
Note:
1.The outdoor failure  can also be indicated by the indoor unit,the checking method as follo-
  ws: LED5  flash times stands for tens digit,and LED1  flash times stands for units digit,
  use this bidigitate figure minus 20,then will get the outdoor error code.For example,if the 
  outdoor error code is 15,LED5 will flash 3 times firstly,two seconds later,LED1 will flash 5
  times , and  four seconds later the process will repeat again.
2.LED5 is a red one on the indoor PCB,LED1 is a yellow one.
3.To get much more details about the out door unit failure,please refer to
the outdoor unit trouble shooting list.
  
INDOOR UNIT TROUBLE SHOOTING
Sensor disconected,or brok-
en,or at wrong position,or
short circuit 
Pump motor disconnected 
or at wrong position,or the
float switch disconnected,
or at wrong position,or the 
short circuit bridge disconne
ted
0150515407
Indoor unit DC fan 
motor abnormal