Domestic air conditioner
11.4.11 Loss of synchronism detection 
Inverter side current detection is abnormal 
Within 3 minutes after the machine is
supplied with power and turned on with
the remote controller, check whethe
the compressor can    start up 
1. The wiring of compressor is incorrect
or the connection is poor;
2. The compressor is damaged
At first, the compressor start up ,soon the 
compressor stopped with the LED1 on the 
outdoor PCB blinks(1Hz)19/18 times 
IPM Module is damaged and needs 
replacing. 
the Malfunctions exist also, the 
compressor is damaged replace a 
new one 
NO 
Malfunction unsolved 
Maybe there is some disturbance 
Method of 
malfunction detection 
Malfunction detection 
conditions 
Troubleshooting 
The position of the compressor rotor can not detected normally 
when the wiring of compressor is wrong or the connection is poor; or the compressor 
is damaged 
■Faulty    The wiring of compressor
■Faulty  compressor
■Faulty  PCB
Supposed causes 
* Caution
Be sure to turn off power switch before connect or disconnect connector,    or else 
parts damage may be occurred. 
LED1  flash 18 times 
LED1  flash 19 times
Outdoor diplay 
Yes 
Yes