Functions and Control
Domestic air conditioner
controlled by the thermostat. The outdoor system can be restarted when the coil temperature is below 42℃
and the system has been stopped for 3 minutes. The malfunction will be stored in the malfunction resume
and will not be revealed.
7.1.13 Abnormal operation of indoor system
When the outdoor system operates, if the indoor system operation differs from the outdoor system, the
abnormal operation malfunction will be reported. 10s after the report, the indoor system will be closed.
Outdoor system mode Indoor system mode conflicts
cooling heating yes
cooling cooling no
cooling airflow no
heating heating no
heating airflow yes
heating cooling yes
7.1.14 Malfunction list resume.
Nothing is presented if there is no code list.
The malfunction display will automatically finish in 10 seconds.
The remote control only receives the signals for stop. According to the signals, the malfunction resume
presentation finishes.
The resume restores after the power supply restores.
7.1.15 Abnormality confirmation approaches
1. indoor temperature sensor abnormality:
Under the operation, the normal temperature ranges from 120 degree to -30 degree. When the temperature
goes beyond this range, the abnormality can be confirmed. If the temperature goes back into the range, the
system will automatically resume.
2 .indoor heat interaction sensor abnormality:
Under the operation, the normal temperature ranges from 120 degree to -30 degree. When the temperature
goes beyond this range, the abnormality can be confirmed. If the temperature goes back into the range, the
system will automatically resume.
3 .indoor malfunction:
Outdoor malfunction: When the indoor system receives the outdoor malfunction codes, it will store the code
into E2 for the malfunction list resume. The indoor system will continue to operate according to the original
status, the malfunction code will not be revealed or processed.
4. transmission abnormality:
If the indoor system can’t receive the outdoor system for 8 minutes, the communication abnormality can be
confirmed and reported and the outdoor system will be stopped.
7.1.16 Single indoor system operation
* Enter condition: First, set the high speed airflow and 30 centigrade set temperature, then press the dormant