EasyManua.ls Logo

HANKISON SPXFLOW HSHD Series - Remote On;Off Settings; Setting Menu

HANKISON SPXFLOW HSHD Series
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
6.5.3 Remote On/Off Settings
Mode A:
With Remote Off, the cycle is stopped, the solenoid valves are
switched off.
With Remote On, the cycle continues at the same point.
Optimized for reciprocating compressors!
Dip switch 6 on OFF.
Mode B:
With Remote Off, the half-cycle is stopped at the end, and the
solenoid valves are switched off.
With Remote On, the cycle continues at the same point.
Optimized for the desiccant dryer!
Dip switch 6 on ON.
Remote On Mode A
A
Remote On Mode B
B
Remote Off Mode A
A
Remote Off Mode B
B
6.5.4 Setting Menu
Press and hold button for approximately 3 seconds.
Target pressure dewpoint
Now appears (Set pressure dewpoint):
PDP sensor installed and activated
-4 0 °F
or
PDP sensor disabled
Pressing
marks the number/symbol in the second line.
By further pressing the
button, the scrolling will continue:
; -80°C/-112°F; -79°C/-110°F; …; -21°C/-5.8°F; -20°C/-4°F;
Meanings:
PDP control switched off
e.g. -40°C/-40°F Target PDP is -40°/-40°F C
Pressure dewpoint alarm
(if PDP sensor installed and activated)
By pressing , you move to (pressure dewpoint alarm):
-4 °F
Pressing
marks the number in the second line.
Press the button
again to scroll through:
The setting range is between (target pressure dewpoint + 5°C/
41°F) and 0°C/32°F.
Example:
Target pressure dewpoint: -37°C/-34,6°F
Pressure dewpoint alarm setting range: -32°C/-25.6°F to 0°C/
32°F
The following options are available:
(-32°C/-25.6°F; -31°C/-23.8°F; …; -1°C/30.2°F; 0°C/32°F;
-32°C/-25.6°F)

Table of Contents

Related product manuals