EasyManua.ls Logo

Harman PF100 - Installation - Power and Draft; Installing Electrical Power; Checking & Recording the Low Draft

Harman PF100
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
3-90-08101R23_06/13
Installing Electrical Power:
Toinstallpowertothefurnacerstremovethecoveronthe
circuitbreakerjunctionboxshown.
Insideyouwillndthemainterminalblock.(Seewiringdiagram
on page 36 for location of main terminal block and proper
powerconnections).Inthebottomoftheboxaknockouthole
isprovidedfortheincomingwire.
The minimum recommendedcircuitis15Amp120V.A.C.60
Hz.Thisfurnaceshouldbetheonlyapplianceonthecircuit.
This furnace should never be powered by the use of an
extension cord.
Therecommendedhighandlowvoltagesare,130V.A.C.60
Hzmaximumhighvoltage,and113V.A.C.60Hzminimum
lowvoltage.
The furnace will continueto operate at voltages as low as
105V.A.C.,althoughitcannotbeguaranteedthatautomatic
ignitionwilloccur.Also,thereisthepossibilityofadistribution
blowermotoroverload.
NOTE: If other sources of electrical power are to be
used (such as a generator) for normal operation or
emergency operation, this source should be checked
before installation. Many generators and inverters may not
supply 120V.A.C. 60Hz. power stable enough to operate
the control board properly. (Control board damage could
occur).
Checking & Recording the Low Draft:
Aftertheventingiscompleted,thereboxlowdraftwillneed
tobecheckedandpossiblyadjusted.Afterremovingthe3/8”
boltfromthedraftholeshowninFig.38,insertthedraftmeter
tube.Theinnerashdoorandthehopperlidmustbelatched
duringthistest.(Itisrecommendedthatthedraftmeterhave
ascaleof0to1”WC.)
TurntheFeedAdjusterto“Test”.thiswillstartthecombustion
blower and allow you to check and record the High Draft
______-IWCdate_______(Thereisnoadjustmentfor
theHighDraft)
After the first 60 seconds, the “Test” mode lowers the
combustionblowervoltagetotheLowBurnvoltage.During
this lowered voltage cycle the Low Burn Draft must be
checked andadjustedifnecessary.Therecommendedlow
draftsettingshouldbebetween-.25&-.35IWC.Depending
ontheamountofverticalrise,itmaynotbepossibletogeta
lowdraftreadinginthisrange.Inthiscase,amaximumlow
draftof-.55isacceptable.
Theadjustmentscrewisthroughthesmallholetotheright
ofthe Igniter Light. See Fig. 39.Adjusted the Low Draft to
__________-IWC.
Don’t forget to turn off of “Test” mode.
Installation
Fig. 38
Draft meter bolt
Furnace Control
“Test”
Low Draft Adjustment Pot
Fig.39
Fig. 37

Related product manuals