EasyManua.ls Logo

Harris DX 25U - Interlock String Operation

Default Icon
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
will bring U60-4 LOW. The LOW input to U60C will force
U60-10 HIGH.
P.7.7.1 Interlock Gate circuit
Eachinterlockcircuit output from U60-1orU60-4islogicLOW
when there is an interlock fault. Each output goes to the LED
Board status indicator circuits at J7-37 and J7-35, and to the
Interlock Gate circuit U51-11, U60-10, U60-13.
The output of U60-4 is inverted to logic HIGH at U60-10 and
U60-1 isinvertedto logicHIGH atU60-13.Thesesignalsaregated
together by U51 and the output at U51-11 will be logic HIGH if
either circuit indicates a fault. This logic HIGH is fed to U51-10.
The other input to U59-9 is a TYPE 1 Fault input from the LED
Board. During a TYPE 1 Fault or Interlock fault, U51-8 will be
logic HIGH. This HIGH generates a latched OFF command
through Q5-7 and inhibits K2 through U52-8.
The output of U51-8 will go HIGH and energize Q5-7 to
generate a latched OFF command.
P.7.8
Interlock String Operation
An Interlock String fault causes a Door Interlock fault
indication. To prevent an External Interlock fault from causing
a Door Interlock fault status output, Q9-7 inhibits the Inter-
lock String input to the Door Interlock status circuit.
P.7.8.1 Interlock String Input
The Interlock Stringinput circuit consists of two sections of Q9.
(Inhibit transistor Q9-7 will be described later; for now, assume
that it remains OFF; that is, its collector is an open circuit.)
The Interlock Status input is normally a logic HIGH input
when interlock relay K3 is energized. The logic HIGH to Q9-9
turns the transistor ON and the collector is pulled LOW. This
will turn Q9-13 OFF, and bring the collector HIGH.
P.7.8.2 Interlock String Fault
An interlock string failure removes the +30 Vdc input to R87.
Resistor R84 grounds Q9-9 and turns the transistor OFF. The
collectorgoes HIGH, Q9-14 goesLOWto startthe delay timer and
after approximately 0.15 seconds a Door Interlock Fault output is
generated.
P.7.8.3 Inhibit Transistor Q9-7
Transistor Q9-7 prevents an Interlock String fault caused by
de-energizing External Interlock relay K3 from generating a
DoorInterlockstatus indication. When anExternal Interlock
fault-H input occurs, both Ext Intlk input transistor Q8 and
Inhibit transistor Q9-7 turn ON. Because Q9-7 is ON, it
pulls the collector line LOW, INHIBITING the Intlk String
Fault-H input to Q9-13.
P.8 +5B Reset Circuit
The +5B Reset circuit is shown on Sheet 1 of the Controller
schematic diagram, along the top. The circuit uses two sections
of an LP339 low-power comparator.
All circuits supplied from the +5B backup supply are specified
to operate reliably at supply voltages as low as +3 Vdc. If the
+5B supply voltage drops below this value, the +5B RESET
circuit generates two RESET signals: +5B RESET-L, a logic
LOW signal and +5B RESET-H, a logic HIGH signal. These
signals reset all latch outputs to zero.
The inverting input of comparator U37-1, at pin 6, is a +1.22 Volt
reference voltage from zener diode CR8. The non-inverting input,
at pin 7, is a sample of the +5B voltage from voltage divider
R19-R20. Feedback resistor R32 introduces some hysteresis, so
that the Fault outputs occur when the +5B supply drops below
approximately +3.1 Vdc and clear again when the +5B supply
increases above approximately +4.2 Vdc.
P.8.1
+5B Reset-L Output (U37-1)
The output of U37-1 goes LOW when the +5B supply drops
belowthecomparatorthreshold, and providesthe+5B RESET-
L logic output.
P.8.2
+5B Reset-H Output (U37-14)
The input to U37-8 is the +5B RESET-L signal, and the
non-inverting input is the +1.22 Volt reference. When U37-1
generates a +5B RESET-L Fault output, the output of U37-14
goes from zero to approximately the +5B supply voltage. This
output is the +5B RESET-H logic signal.
Figure P-8. Control Board "Supply Fault"
(Regulator Fault) Circuit, Simplified Diagram (817 1280 097)
Section P - Controller (A38)
Rev. S: 05-02-97 888-2297-002 P-17
WARNING: Disconnect primary power prior to servicing.

Table of Contents

Related product manuals