Engineering Design Guide HBH SERIES Heat Controller, Inc.
6
Performance Data
AHRI/ASHRAE/ISO 13256-1
ASHRAE/AHRI/ISO 13256-1 English (I-P) Units
ASHRAE/AHRI/ISO 13256-1 Metric (S-I) Units
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Cooling 77°F Heating 32°F
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
HBH072
69,000 13.3 92,500 5.0 78,500 19.7 75,500 4.4 71,000 14.6 58,000 3.5
HBH096
95,000 13.7 123,000 5.0 104,500 20.0 101,000 4.4 98,000 15.2 77,000 3.6
HBH120
119,000 13.3 160,000 4.6 134,000 19.3 132,500 4.0 122,500 14.5 103,000 3.3
Note 1: All HBH072 ratings @ 2400CFM (1133 l/s) w/20GPM (1.26 l/s). Sheave setting for AHRI is 2.5 turns open.
Note 2: All HBH096 ratings @ 3200CFM (1510 l/s) w/24GPM (1.51 l/s). Sheave setting for AHRI is 3.0 turns open.
Note 3: All HBH120 ratings @ 4000CFM (1888 l/s) w/30GPM (1.89 l/s). Sheave setting for AHRI is 3.0 turns open.
Note 4: Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature.
Note 5: Heating capacities based upon 68°F DB, 59°F WB entering air temperature.
Note 6: All ratings based upon operation at lower voltage of dual voltage rated models.
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C Cooling 25°C Heating 0°C
Capacity
kW
EER
W/W
Capacity
kW
COP
Capacity
kW
EER
W/W
Capacity
kW
COP
Capacity
kW
EER
W/W
Capacity
kW
COP
HBH072
20,223 3.9 27,110 5.0 23,007 5.8 22,128 4.4 20,809 4.3 16,999 3.5
HBH096
27,843 4.0 36,049 5.0 30,627 5.9 29,601 4.4 28,722 4.5 22,567 3.6
HBH120
34,877 3.9 46,893 4.6 39,273 5.7 38,834 4.0 35,903 4.2 30,188 3.3
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature.
Heating capacities based upon 68°F DB, 59°F WB entering air temperature.
All ratings based upon operation at lower voltage of dual voltage rated models