Engineering Design Guide HBH SERIES Heat Controller, Inc.
5
HBH Series Nomenclature
HB H A0 9 6 C4 3 A C S
1 2 3 4 5 6 7
8
9101112 13
HB = Heat Controller Compact
Model Type
H = Horizontal
Configuration
072
Unit Size
096
120
Revision Level
A = Current Revision
Voltage
C = CXM
Controls
1 = Commercial Extended Range
Cabinet
2 = Commercial Extended Range w/UltraQuiet
Blower Drive Package
Heat Exchanger Options
L = Left Return
Return Air Flow Configuration
R = Right Return
V = Left Return, S.S. Drain Pan
C = Copper Water Coil, Non Coated Air Coil
N = Cupro-Nickel Water Coil, Non Coated Air Coil
A = Copper Water Coil, E-Coated Air Coil
J = Cupro-Nickel Water Coil, E-Coated Air Coil
3 = Commercial Standard Range
W = Right Return, S.S. Drain Pan
4 = Commercial Standard Range w/UltraQuiet
A = Standard RPM & Standard Motor
B = Low RPM & Standard Motor
C = High RPM & Standard Motor
D = Standard RPM & Large Motor
E = High RPM & Large Motor
3 = 208-230/60/3
4 = 460/60/3
5 = 575/60/3
S = Straight Supply
Supply Air Flow Configuration
B = Back Supply
L
14
HBH Large Model Structure
Basic Unit Description:
The basic unit price includes sealed heat pump refrigerant circuit
and air handler within cabinetry, lter, and a factory installed hang-
er kit on horizontal units.
Cabinetry - Compact design - galvanized steel construction -
FPT water connections, high and low voltage knockouts - lter
and lter brackets. All horizontal units have eld convertible
discharge air patterns, no extra parts required.
Standard Controls - CXM Controller, loss of charge switch, high
pressure switch, water coil low temperature cutout, lockout
safety circuit reset at thermostat or disconnect, LED fault indi-
cation, ve minute anti-short cycle, random start, high and low
voltage protection, condensate over ow protection, dry contact
for alarm.
Compressor - High ef ciency scroll compressor - overload
protected.
Refrigerant Circuit - Dual refrigerant circuit. Thermostatic ex-
pansion valve’s for refrigerant metering, copper tubing intercon-
necting all components - sealed & tested non-ozone depleting,
R-410A refrigerant circuit with high and low-side Schrader ports.
Reversing Valve - 4-way, pilot operated, solenoid activated in
cooling.
Water to Refrigerant Coil - Tube-in-tube, convoluted copper
inner water tube.
Refrigerant to Air Coil - Lanced aluminum ns on ri ed copper
tubes.
Blower Motor - Belt drive with adjustable sheave, single blower
and single blower motor.
Application - Units can be applied in WLHP, GWHP or GLHP
applications.
Field Connections - For supply, return and condensate can be
made on either side (plug opposite side). Condensate connec-
tion on end opposite compressor end.