36EPU‐DInstallationandOperationManual
059840‐00Rev.A Heat‐TimerCorp.
SystemTrim
OutdoorTrim
FastCycleTest
Selections:-5°F/-20°Cto5°F/-15°C Default:0°F/-18°C
MenuPath:/Maintenance>SystemTrim
AvailableWhen:SystemSensorType=HeatingSystemSensor
Description:
Thisoptionallowsfineadjustmentstobemadetothedisplayedvalueoftheheatingsystemsensor
temperaturereading.
Selections:-5°F/-20°Cto5°F/-15°C Default:0°F/-18°C
MenuPath:/Maintenance>OutdoorTrim
Description:
Thisoptionallowsfineadjustmentstobemadetothedisplayedvalueoftheoutdoorsensortemperature
reading.
NOTE:Onlytrimtheoutdoorsensorbasedonanaccuratethermometerreadingtakenwherethesensoris
located.
Selections:Off,On Default:Off
MenuPath:/Maintenance>FastCycle
Description:
Thisoptionallowsfortestingtheboilerburnerormotorizedvalve.IfThermalLockoutisnotactive,thecontrol
willturnontheboilerburneroropenthemotorizedvalve.
NOTE:FastCyclewillonlyfunctionwhentheEPU‐Disinacycle.ItwillnotoverridetheHeatEstablished
functionorpreventThermalLockout.
WhenOnisselected,thecontrolchangescycleminutestocycleseconds,allowinga60minutecycletobe
viewedin60seconds.
NOTE:BesuretoturnofftheFastCycleeitherusingtheFastCycleTestmenu,orCancelFastCyclemenu
(seepage 28).