Table 5 – Air Delivery CFM (with filter)*
Unit Size Operating Mode
CFM
Airflow
Setting
External
Static
Pressure
Range*
(In. W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
0701412 AIRFLOW (CFM)
†† Low Heat 735† 00.50 735 735 735 735 725
High Heat 1180† 01.0 1160 1165 1175 1180 1180 1180 1180 1180 1180 1175
†† 11/2Ton Cooling 525 00.50‡ 515 500 500 490 485
†† 2Ton A/C Cooling 700 00.50‡ 690 680 675 680 675
21/2Ton A/C Cooling 875 01.0‡ 875 875 875 870 865 855 850 835 825 820
3Ton A/C Cooling 1050 01.0‡ 1050 1050 1050 1050 1050 1050 1045 1035 1020 1000
31/2Ton A/C Cooling 1225 01.0 1220 1225 1225 1225 1225 1220 1205 1190 1185 1170
Maximum 1400 01.0 1395 1400 1400 1400 1395 1385 1370 1340 1300 1245
0901716
Low Heat 985† 01.0 950 970 985 985 985 985 985 985 985 980
High Heat 1210† 01.0 1190 1205 1210 1210 1210 1210 1210 1210 1210 1200
†† 11/2Ton A/C Cooling 525 00.50‡ 525 520 525 495 475
†† 2Ton A/C Cooling 700 00.50‡ 680 680 680 675 670
21/2Ton A/C Cooling 875 01.0‡ 815 845 845 855 850 850 845 835 820 805
3Ton A/C Cooling 1050 01.0‡ 1005 1005 1015 1035 1040 1040 1035 1030 1025 1010
31/2Ton A/C Cooling 1225 01.0 1190 1200 1200 1205 1205 1215 1205 1200 1185 1170
4Ton A/C Cooling 1400 01.0 1350 1370 1390 1390 1400 1390 1380 1380 1360 1340
Maximum 1600 01.0 1595 1600 1600 1600 1595 1555 1505 1465 1430 1390
1102120***
Low Heat 1320† 01.0 1275 1295 1315 1320 1320 1320 1320 1320 1320 1315
High Heat 1475† 01.0 1460 1465 1475 1475 1475 1475 1475 1475 1465 1465
†† 2Ton A/C Cooling 700 00.50‡ 700 700 700 700 700
†† 21/2Ton A/C Cooling 875 00.50‡ 875 875 875 875 875
†† 3Ton A/C Cooling 1050 00.50‡ 1050 1050 1050 1050 1050
31/2Ton A/C Cooling 1225 01.0‡ 1225 1225 1225 1225 1225 1225 1225 1225 1225 1225
4Ton A/C Cooling 1400 01.0‡ 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400
5Ton A/C Cooling 1750 01.0‡ 1750 1750 1750 1750 1750 1750 1750 1750 1740 1725
6Ton A/C Cooling 2100 01.0 2100 2100 2100 2100 2090 2075 2055 2040 2005 1970
Maximum 2200 01.0 2200 2190 2190 2180 2155 2145 2125 2100 2080 2020
1352422
Low Heat 1700† 01.0 1700 1700 1700 1700 1700 1695 1700 1695 1685 1670
High Heat 1915† 01.0 1900 1905 1915 1915 1915 1915 1915 1915 1915 1915
†† 2Ton A/C Cooling 700 00.50‡ 700 700 700 700 665
†† 21/2Ton A/C Cooling 875 00.50‡ 870 870 865 865 865
†† 3Ton A/C Cooling 1050 00.50‡ 1010 1030 1050 1050 1050
31/2Ton A/C Cooling 1225 01.0‡ 1155 1180 1200 1210 1220 1225 1225 1225 1225 1225
4Ton A/C Cooling 1400 01.0‡ 1395 1400 1400 1400 1400 1400 1400 1390 1375 1355
5Ton A/C Cooling 1750 01.0‡ 1740 1750 1750 1750 1735 1740 1735 1730 1715 1700
6Ton A/C Cooling 2100 01.0 2075 2085 2090 2100 2100 2100 2090 2080 2055 2025
Maximum 2200 01.0 2180 2195 2200 2200 2200 2200 2185 2165 2140 2095
Air DeliveryCFM Notes
*Actual external static pressure (ESP) can be determined by using the fan laws (CFM 2 proportional to ESP); such as, a system with 1180 CFM at 0.5
ESP would operate at cooling airflow of 1050 CFM at 0.4 ESP and lowheating airflow of 735 CFM at 0.19 ESP.
Efficiency airflow are shown in parenthesis. Efficiency is selected when the lowheat rise adjustment switch (SW13) is OFF and the comfort/effi-
ciency switch (SW14) is OFF.
Ductwork must be sized for highheating CFM within the operational range of ESP.
Operation within the blank areas of the chart is not recommended because highheat operation will be above 1.0 ESP.
***All airflow on 110 size furnace are 5% less on side return only installations.