Maintenance | 25
11. Maintenance
To be able to guarantee the
impeccable function of the smoke
alarm, an on-site inspection including
functional test is to be carried at
least once a year (12 ± 3 months),
in accordance with the national
directives and regulations (in Germany
in accordance with DIN 14676-1).
During the functional test, the
smoke alarm determines whether
its operational readiness can be
guaranteed for the next 15 months
and signalises its corresponding
status by means of the test button
and the acoustic alarm.
The smoke alarm is not suitable
for using test gas.
f Only carry out the functional
test by pressing the test
button.
Carrying out maintenance
f Remove the dust from the smoke
alarm with a soft cloth.
f If required, remove any
contamination with a wet cloth.
Do not use detergents.
f Ensure the following points:
The smoke alarm is not
damaged.
There is a clearance of > 0.5 m
around the smoke alarm.
The smoke inlets are not
obstructed.
The opening for the acoustic
alarm is not obstructed.
All rooms prescribed by
law
have asmoke alarm
(seechapter“Project planning”)