Before You Start
Go to
Conguration > System > Maintenance > VCA Resource Type , select Temperature
Measurement + Fire and Smoke Detection.
Steps
1.
Go to Conguration > Event > Smart Event , select Fire and Smoke Detection.
2.
Check Enable Fire and Smoke Detection.
3.
Select Fire and Smoke Detection Mode.
Detection Mode Mode Description Conguration Description
Fire or Smoke The system alarms when
device is triggered either by
Fire Source Detection or
Smoke Detection.
Set Fire Source Detection
and Smoke Detection, see
step 4.
Fire and Smoke The system alarms when
device is triggered both by
Fire Source Detection and
Smoke Detection or either
of them.
Double Conrm The system alarms when
device is triggered both by
Fire Source Detection and
Smoke Detection.
Specied Fire Source The system alarms when
device is triggered only by
Fire Source Detection.
Set Fire Source Detection,
see step 4.
Specied Smoke The system alarms when
device is triggered only by
Smoke Detection.
Set Smoke Detection, see
step 4.
Note
Fire or Smoke, Fire and Smoke and Double Conrm are mutually exclusive with
temperature measurement function.
4.
Set Fire Source Detection and Smoke Detection.
Detection
Function
Parameter Description
Fire Source
Detection
Alarm Interval
Set the alarm interval between two alarms. The smaller the value is,
the higher the detection frequency is.