HI 800 101 HIMatrix Engineering Manual
9.2 Mechanical Conditions
The most important tests and limit values for mechanical conditions are listed in the following
table:
IEC/EN 61131-2
Chapter 6.3.5
Mechanical Tests
Vibration test, operating:
5...9 Hz / 3.5 mm
9...150 Hz / 1 g
6.3.5.1
Immunity vibration test:
10...150 Hz, 1 g, EUT operating, 10 cycles per axis
6.3.5.2
Immunity shock test:
15 g, 11 ms, EUT operating, 2 cycles per axis
9.3 EMC Conditions
The most important tests and limit values for EMC conditions are listed in the following ta-
bles:
IEC/EN 61131-2
Chapter 6.3.6.2
Noise Immunity Tests
6.3.6.2.1
IEC/EN 61000-4-2
ESD test: 4 kV contact / 8 kV air discharge
6.3.6.2.2
IEC/EN 61000-4-3
RFI test (10 V/m): 26 MHz...1 GHz, 80 % AM
6.3.6.2.3
IEC/EN 61000-4-4
Burst test: 2 kV power supply / 1 kV signal lines
6.3.6.2.4
IEC/EN 61000-4-12
Damped oscillatory wave immunity test: 1 kV
IEC/EN 61000-6-2 Noise Immunity Tests
IEC/EN 61000-4-6
Radio frequency common mode:
10 V, 150 kHz...80 MHz, AM
IEC/EN 61000-4-3 900 MHz pulses
IEC/EN 61000-4-5 Surge: 1 kV, 0.5 kV
IEC/EN 61000-6-4 Noise Emission Tests
EN 50011
Class A
Emission test:
radiated, conducted