4 Start-up  X-CPU 01 
Page 40 of 52  HI 801 009 E Rev. 4.00 
Column  Description  Range of Values 
LL Alarm Priority  Priority of the lowest limit; default value: 500  0...1000 
LL Alarm 
Acknowledgment 
Required 
Activated 
The user must confirm that the lowest limit value 
has been exceeded (acknowledgment). 
Deactivate
d 
The user may not confirm that the lowest limit 
value has been exceeded. 
Default value: Deactivated 
Checkbox activated, 
deactivated 
Alarm Hysteresis 
The hysteresis avoids that many events are continuously 
created when the process value often oscillate around a limit. 
depending on the 
global variable type 
Table 23:  Parameters for Scalar Events 
 
NOTICE
 
 
Faulty event recording due wrong parameter settings possible! 
Setting the parameters L Alarm Value and H Alarm Value to the same value can 
cause an unexpected behavior of the event recording since no normal range exists 
in such a case. 
For this reason, make sure that L Alarm Value and H Alarm Value are set to different 
values. 
 
 
4.1.6 User Program 
Which application function the PES should perform is specified in the user program. The 
PADT is used to create and compile the project configuration with the user program, and to 
load it into the processor module. 
4.1.7 Starting the Processor Module 
The processor module can be started as described below: 
  Inserting it into a base plate supplied with operating voltage 
  Switching on the operating voltage for the base plate in which the module is inserted. 
The module's behavior while it is starting up depends on: 
  Position of the mode switch (see 
3.4.18) 
  Existence of additional, redundant processor modules 
  Existence of a valid project configuration (user programs included) in the non-volatile 
memory 
With the switch set to Stop or Run, the processor  module checks if any other processor 
modules exist 
  If no other processor modules exist, the module starts operation alone. 
  If at least one additional processor module exists, the module attempts to automatically 
start operation using the configuration of the existing processor module(s). Safety-
related operation is maintained. 
For more information on how to start up modules, refer to the HIMax System Manual 
(HI 801 001 E). 
The instructions specified in the Safety Manual (HI 801 003 E) must also be observed.