EasyManua.ls Logo

HIMA HIMax X-DI 32 02 - Page 18

HIMA HIMax X-DI 32 02
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Product Description X-DI 32 02
Page 18 of 56 HI 801 017 E Rev. 4.00
CAUTION
If three-fold redundant modules (TMR) are used, reverse polarity on the safety
proximity switches is no longer detected as short-circuit.
Proximity switch supply
Number of proximity switch
supplies
4 with 8 outputs each
Output voltage for proximity
switch supply
8.2 VDC, ± 6 %
Monitoring of the proximity
switch supply
The module monitors the proximity switch supplies for
overvoltage, undervoltage and overcurrent.
If a fault occurs, the corresponding Channel X Supply
OK status is set to FALSE.
Short-circuit of a proximity
switch supply
> 200 mA (0 V per module)
The module switches off the affected proximity switch
supply and sets the corresponding Supply OK status to
FALSE.
Maximum overload duration of
the short-circuit (S+ -> DI+)
60 s
Assignment of the supply outputs
For supplying, the voltage output assigned to the input must be used.
S1+...S8+ DI1+…DI8+
S9+...S16+ DI9+…DI16+
S17+...S24+ DI17+…DI24+
S25+...S32+ DI25+…DI32+
Table 10: Product Data of the Proximity Switch Supply