4 Start-up X-DI 32 02
Page 40 of 56 HI 801 017 E Rev. 4.00
Name Data type R/W Description
Toff [µs] UDINT R Time off delay
The module only indicates a level change from HIGH to LOW if the
LOW level is present for longer than the configured time t
off
.
Important: The maximum reaction time T
R
(worst case) for this
channel is extended by the delay time, since a signal change is
not detected until the delay time has expired.
Range of values: 0...(2
32
- 1)
Default setting: 0
-> Raw value
[DINT
DINT R Unhandled analog value measured for the channel
Range of values: 0…93 000 (0…9.3 mA)
Redund. BOOL R Requirement: The redundant module must be configured.
Acivated: Activate the channel redundancy for this channel
Deactivated: Deactivate the channel redundancy for this channel
Default setting: Deactivated
Redundancy
value
BYTE W Setting for determining the redundancy value.
Min
Max
Average
Default setting: Max
It is only displayed in the redundancy group tab!
Table 23: Tab I/O Submodule D32_02: Channels in the Hardware Editor
4.3.4 Submodule Status [DWORD]
Coding of the Submodule Status
Coding Description
0x00000001 Hardware unit fault (submodule).
0x00000002 Reset of an E/A bus
0x00000004 Fault detected while initializing the hardware unit
0x00000008 Fault detected while verifying the coefficients
0x00000080 Reset of the chip select monitoring
0x20000000 Faulty operating voltages
0x40000000 Fault during AD conversion (conversion begin)
0x10000000 Fault during AD conversion (conversion end)
Table 24: Submodule Status [DWORD]