X-DI 32 02 3 Product Description
HI 801 017 E Rev. 4.00 Page 29 of 56
The system cable is available in three variants, see Table 18.
System cable Description Length
X-CA 002 01 8 8 m
X-CA 002 01 15 15 m
X-CA 002 01 30
Coded cable plugs on both sides
30 m
Table 18: Available System Cables X-CA 002
3.7.2 System Cable X-CA 009
The X-CA 009 system cable is used to connect the X-CB 005 05 connector board to the
field zone via field termination assembly.
General
Cable LIYCY-TP 58 x 2 x 0.14 mm²
Wire Finely stranded
Average outer diameter (d) approx. 18.3 mm
Minimum bending radius
Fixed laying
Flexible application
5 x d
10 x d
Combustion behavior
Flame resistant and self-extinguishing in
accordance with IEC 60332-1-2, -2-2
Length 8…30 m
Color coding Based on DIN 47100, see Table 16.
Table 19: Cable Data X-CA 009
The system cable is available in three variants, see table:
System Cable Description Length
X-CA 009 01 8 8 m
X-CA 009 01 15 15 m
X-CA 009 01 30
Coded cable plugs on both sides
30 m
Table 20: Available System Cables X-CA 009
3.7.3 Cable Plug Coding
The cable plugs are equipped with three coding pins. Cable plugs only match connector
boards and FTAs with the corresponding recesses, see
Figure 7.