Installation EAGLE One
Release
03
07/2014
45
EMC and immunity
Note: You will find detailed information on the certificates and declarations applying to your device in a separate
overview.
See table 3 on page 21.
Stability Standard
applications
Navy applications Railway
applications
Substation
applications
IEC 60068-2-6, test Fc Vibration 5 Hz ... 8.4 Hz with
0.14 in. (3.5 mm)
amplitude
2 Hz ... 13.2 Hz
with
0.04 in. (1 mm)
amplitude
— 2 Hz ... 9 Hz with
0.12 in. (3 mm)
amplitude
————
8.4 Hz ... 150 Hz
with 0.04 oz (1 g)
13.2 Hz ... 100 Hz
with 0.03 oz (0.7 g)
— 9 Hz ... 200 Hz
with 0.04 oz (1 g)
————
— — — 200 Hz ... 500 Hz
with 0.05 oz (1.5 g)
IEC 60068-2-27, test Ea Shock 0.53 oz (15 g) at
11 ms
— 0.53oz (10g) at
11 ms
EMC interference
emission
Standard
applications
Navy applications Railway
applications
(trackside)
Substation
applications
Radiated emission
EN 55022 Class A Class A Class A Class A
GL Guidelines — EMC 1 — —
FCC 47 CFR Part 15 Class A Class A Class A Class A
EN 61000-6-4 Fulfilled Fulfilled Fulfilled Fulfilled
Conducted emission
EN 55022 AC and DC supply connections Class A Class A Class A Class A