EasyManua.ls Logo

Hirschmann EAGLE One - Electrical Safety and Grounding

Hirschmann EAGLE One
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
Installation EAGLE One
Release
03
07/2014
See “Technical data” on page 42.
Connect to the product only components suitable for the requirements
of the specific application case.
National and international safety regulations
Verify that the electrical installation meets local or nationally applicable
safety regulations.
Grounding the device
Grounding the device is by means of a separate ground connection on the
device.
Ground the device before connecting any other cables.
Disconnect the grounding only after disconnecting all other cables.
The overall shield of a connected shielded twisted pair cable is connected
to the ground connector on the front panel as a conductor.
Working voltage
The working voltage is electrically isolated from the housing.
Connect only a working voltage that corresponds to the type plate of
your device.
Every time you connect the electrical conductors, make sure that the
following requirements are met:
The power supply conforms to overvoltage category I or II.
The power supply has an easily accessible disconnecting device
(e.g., a switch or a plug). This disconnecting device is clearly
identified. So in the case of an emergency, it is clear which
disconnecting device belongs to which power supply cable.
The electrical wires are voltage-free.
The power supply is Class 2 compliant.
The working voltage inputs are designed for operation with safety
extra-low voltage. Connect only SELV circuits with voltage
restrictions in line with IEC/EN 60950-1 to the working voltage
connections.
Supply with AC voltage:
A fuse is located in the outer conductor of the power supply.
The neutral conductor is on ground potential. Otherwise, a fuse is
also located in the neutral conductor.
Regarding the properties of this fuse: See “General technical data”
on page 42.

Related product manuals