Installation GREYHOUND Switch
Release
01
04/2016
65
EMC and immunity
EMC interference
emission
Standard
applications
a
a. EN 61131-2, CE, FCC – applies to all devices
Merchant Navy
b
b. Merchant Navy – applies to devices with the approval codes U9, UT, UX, UY, VU
Railway
applications
(trackside)
c,d
c. EN 50121-4, EN 50155 – applies to devices with the approval codes VT, T9, TY, S9, SY
d. EN 50155 applies to devices with the approval codes S9, SY
Substation
applications
e
e. EN 61850-3, IEEE 1613 – applies to devices with the certification codes V9, VY, VU, VT
Radiated emission
EN 55022 Class A Class A Class A Class A
GL Guidelines EMC 1
FCC 47 CFR Part 15 Class A Class A Class A Class A
EN 61000-6-4 Fulfilled Fulfilled Fulfilled Fulfilled
Conducted emission
EN 55022 DC supply connection Class A Class A Class A Class A
GL Guidelines DC supply connection EMC 1
FCC 47 CFR Part 15 DC supply connection Class A Class A Class A Class A
EN 61000-6-4 DC supply connection Fulfilled Fulfilled Fulfilled Fulfilled
EN 55022 Telecommunication connections Class A Class A Class A Class A
EN 61000-6-4 Telecommunication connections Fulfilled Fulfilled Fulfilled Fulfilled
EMC interference
immunity
Standard
applications
a
Merchant Navy
b
Railway
applications
(trackside)
c
Substation
applications
d
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge ± 4 kV ± 6 kV ± 6 kV ± 8 kV
EN 61000-4-2
IEEE C37.90.3
Air discharge ±8kV ±8kV ±8kV ±15kV