Measure signal from angle transducer in cable reel. The return signal is a current
output and must be measured in series. Set Voltmeter to measure amps. Remove
Wire #4 from X1:4 in the cable reel and connect one voltmeter lead to wire #4 and
the other lead to X1:4. The measurement should be between 4-20ma. 20ma with the
boom at 0° or 4ma with the boom a 90° .
Refer to system wiring diagram.
Faulty wiring between central unit and cable reel.
Check wiring
Refer to system wiring diagram.
PREVIOUS PAGE
END
Correct?
NO
YES
Replace angle sensor.
Refer to system wiring diagram and sensor
adjustment procedure.
Correct?
NO
Measure signal from angle transducer in central unit. The return signal is a current
output and must be measured in series. Set Voltmeter to measure amps. Remove
Wire #4 from X1:35 in the central unit and connect one voltmeter lead to wire #4 and
the other lead to X1:35. The measurement should be between 4-20ma. 20ma with
the boom at 0° or 4ma with the boom at 90°. Connect wire 4 to terminal X1:35.
Refer to system wiring diagram.
YES