• Controller chassis: 4
• Drive chassis:
○ SFF: 16
○ LFF: 16
○ FMD: 8
Required number of PDUs per rack:
• Controller rack
○ Single phase: 4
○ Three phase: 2
• Drive rack:
○ Single phase: 4
○ Three phase: 2
Environmental specifications
The table lists the environmental specifications and requirements for the
storage system.
Table 18 VSP G1000, VSP G1500, and VSP F1500 environmental
specifications
Item
Operating
1
Not Operating
2
Shipping & Storage
3
Standard Temperature
(ºF / ºC)
61 to 90 / 16 to 32 -18 to 122
-10 to 35
-45 to 110 / -25 to 60
high temperature mode
(ºF / ºC)
60.8 to 104 / 16 to 40
Relative Humidity (%)
4
20 to 80 8 to 90 5 to 95
Max. Wet Bulb (ºF / ºC) 78.8 / 26 80.6 / 27 84.2 / 29
Temperature deviation
per hour (ºF / ºC)
50 / 10 50 / 10 68 / 20
Vibration
6
5 to 10Hz: 0.25 mm10 to
300Hz: 0.49m/s2
5 to 10Hz: 2.5mm10 to
70Hz: 4.9m/s270 to 99Hz:
0.05mm99 to 300Hz:
9.8m/s2
Sine Vibration: 4.9m/s2,
5min.At the resonant
frequency with the highest
displacement found
between 3 to 100Hz
7
Random Vibration:
0.147m2/s3, 30min, 5 to
100Hz
7
Shock No impact 78.4m/s
2
(8.0G) 15ms Horizontal: Incline Impact
1.22m/s
8
Vertical: Rotational Edge
0.15m
10
Dust Less than 0.15mg per cubic
meter of air
- -
Altitude -60 m to 3,000 m -
Site preparation 83
Hitachi Virtual Storage Platform G1000, G1500, and Virtual Storage Platform F1500 Hardware Guide