21
A081 AVR function select
00 AVR enabled 01 AVR disabled
02 AVR enabled except during decel
00
A082 AVR voltage select 230 / 230
400 / 460
A092/
A292
Acceleration (2) time setting 15.0
A093/
A293
Deceleration (2) time setting 15.0
A094/
A294
Select method to switch to Acc2/Dec2 profile
00 2CH input from terminal
01 transition frequency
00
A095/
A295
Acc1 to Acc2 frequency transition point 0.0
A096/
A296
Dec1 to Dec2 frequency transition point 0.0
A097 Acceleration curve selection
00 Linear 01 S-curve
00
A098 Deceleration curve selection
00 Linear 01 S-curve
00
A101 [OI]–[L] input active range start frequency 0.0
A102 [OI]–[L] input active range end frequency 0.0
A103 [OI]–[L] input active range start current 0.0
A104 [OI]–[L] input active range end current 100.
A105 [OI]–[L] input start frequency enable 01
A141 A input select for calculate function
00 Digital operator
01 Keypad potentiometer
02 [O] input
03 [OI] input
04 Network variable
02
A142 B input select for calculate function
00 Digital operator
01 Keypad potentiometer
02 [O] input
03 [OI] input
04 Network variable
03
A143 Calculation symbol
00 ADD (A input + B input)
01 SUB (A input – B input)
02 MUL (A input x B input)
00
A145 ADD frequency 0.0
Func.
Code
Name / Description
Default
Val ue
–FE(F)/–FU
Set
Val ue