22
“B” Group: Fine-tuning Functions
A146 ADD direction select
00 Plus (adds A145 value to output frequency)
01 Minus (subtracts A145 value from output
frequency)
00
A151 Pot. input active range start frequency 0.0
A152 Pot. input active range end frequency 0.0
A153 Pot. input active range start current 0.0
A154 Pot. input active range end current 0.0
A155 Pot. input start frequency enable 01
Func.
Code
Name / Description
Default
Value
–FE(F)/–FU
Set
Value
B001 Selection of automatic restart mode
00 Alarm output after trip, automatic restart
disabled
01 Restart at 0Hz
02 Resume operation after frequency
matching
03 Resume previous freq. after freq. matching,
then decelerate to stop and display trip info
00
B002 Allowable under-voltage power failure time 1.0
B003 Retry wait time before motor restart 1.0
B004 Instantaneous power failure / under-voltage trip
alarm enable
00 Disable
01 Enable
00
B005 Number of restarts on power failure / under-
voltage trip event
00 Restart 16 times
01 Always restart
00
B012/
B212
Level of electronic thermal setting Rated
current of
each inverter
B013/
B213
Electronic thermal characteristic
00 Reduced torque1 01 Const. torque
02 Reduced torque2
01
Func.
Code
Name / Description
Default
Value
–FE(F)/–FU
Set
Value