Chapter 4 List of Data Settings
4 - 3
Code Function name Monitored data or setting Default
Setting
during
operation
(allowed
or not)
Change
during
operation
(allowed
or not)
d025 User monitor 0 -2147483647 to 2147483647 (upper 4 digits including “-“) − − −
d026 User monitor 1 -2147483647 to 2147483647 (upper 4 digits including “-“) − − −
d027 User monitor 2 -2147483647 to 2147483647 (upper 4 digits including “-“) − − −
d028 Pulse counter 0 to 2147483647 (upper 4 digits) − − −
d080 Trip Counter 0. to 9999., 1000 to 6553 (10000 to 65530) (times) − − −
d081 Trip monitoring 1
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
d082 Trip monitoring 2
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
d083 Trip monitoring 3
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
d084 Trip monitoring 4
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
d085 Trip monitoring 5
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
d086 Trip monitoring 6
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
− − −
d090 Programming error monitoring Warning code − − −
d102 DC voltage monitoring 0.0 to 999.9 (V) − − −
d103 BRD load factor monitoring 0.0 to 100.0 (%) − − −
d104 Electronic thermal overload monitoring 0.0 to 100.0 (%) − − −
4.3 Function Mode
Code Function name Monitored data or setting
Default
Setting
during
operation
(allowed
or not)
Change
during
operation
(allowed
or not)
_FF
F001 Output frequency setting
0.0, "start frequency" to "maximum frequency"
(or maximum frequency, 2nd/3rd motors) (Hz)
0.0 to 100.0 (when PID function is enabled)
0.00 { {
F002 Acceleration (1) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00 { {
F202 Acceleration (1) time setting, 2nd motor 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00 { {
F302 Acceleration (1) time setting, 3rd motor 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00 { {
F003 Deceleration (1) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00 { {
F203 Deceleration time setting, 2nd motor 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00 { {
F303 Deceleration time setting, 3rd motor 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00 { {
F004 Keypad Run key routing 00 (forward rotation), 01 (reverse rotation) 00 ¯ ¯