Chapter 4 List of Data Settings
4 - 4
4.4 Extended Function Mode
Code Function name Monitored data or setting
Default
Setting
during
operation
(allowed
or not)
Change
during
operation
(allowed
or not)
_FF
Basic settings
A001 Frequency source setting
00 (keypad potentiometer) (*1), 01 (control circuit terminal block),
02 (digital operator), 03 (RS485), 04 (option 1), 05 (option 2),
06 (pulse-string input), 07 (easy sequence),
10
operation function result
02
¯ ¯
A002 Run command source setting
01 (control circuit terminal block), 02 (digital operator), 03 (RS485),
04
02
¯ ¯
A003
Base frequency setting 30. to "maximum frequency " (Hz)
60.
¯ ¯
A203
Base frequency setting, 2nd moto
30. to "maximum frequency, 2nd moto
" (Hz)
60.
¯ ¯
A303
Base frequency setting, 3rd moto
30. to "maximum frequency, 3rd moto
" (Hz)
60.
¯ ¯
A004
Maximum frequency setting 30. to 400. (Hz)
60.
¯ ¯
A204
Maximum frequency setting, 2nd moto
30. to 400. (Hz)
60.
¯ ¯
A304
Maximum frequency setting, 3rd moto
30. to 400. (Hz)
60.
¯ ¯
Analog input and others
A005 [AT] selection
00 (switching between O and OI terminals),
01 (switching between O and O2 terminals),
02 (switching between O terminal and keypad potentiometer) (*1),
03 (switching between OI terminal and keypad potentiometer) (*1),
04
00
¯ ¯
A006 [O2] selection
00 (single),
01 (auxiliary frequency input via O and OI terminals) nonreversible),
02 (auxiliary frequency input via O and OI terminals) (reversible),
03
03
¯ ¯
A011
[O]-[L] input active range start frequency 0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯ {
A012
[O]-[L] input active range end frequency 0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯ {
A013
[O]-[L] input active range start voltage 0. to "[O]-[L] input active range end voltage" (%)
0.
¯ {
A014
[O]-[L] input active range end voltage "[O]-[L] input active range start voltage" to 100. (%)
100.
¯ {
A015
[O]-[L] input active range start frequency
selection
00 (external start frequency), 01 (0 Hz) 01
¯ {
A016
External frequency filter time const. 1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis)
31.
¯ {
A017
Easy sequence function selection 00 (disabling), 01 (enabling)
00
¯ ¯
Multispeed operation and jogging
A019 Multispeed operation selection
00 (binary: 16 speeds selectable with 4 terminals),
01
bit: 8 speeds selectable with 7 terminals
00
¯ ¯
A020
Multispeed frequency setting 0.0 or “start frequenc
” to “maximum frequency” (Hz)
0.00
{ {
A220
Multispeed frequency setting, 2nd moto
” to “maximum frequency, 2nd moto
”(Hz)
0.00
{ {
A320
Multispeed frequency setting, 3rd moto
” to “maximum frequency, 3rd moto
”(Hz)
0.00
{ {
A021
Multispeed 1 setting 0.0 or “start frequenc
” to “1st maximum frequenc
”(Hz)
0.00
{ {
A022
Multispeed 2 setting 0.0 or “start frequenc
” to “2nd maximum frequenc
”(Hz)
0.00
{ {
A023
Multispeed 3 setting 0.0 or “start frequenc
” to “3rd maximum frequenc
”(Hz)
0.00
{ {
A024
Multispeed 4 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A025
Multispeed 5 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A026
Multispeed 6 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A027
Multispeed 7 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A028
Multispeed 8 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A029
Multispeed 9 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A030
Multispeed 10 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A031
Multispeed 11 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A032
Multispeed 12 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A033
Multispeed 13 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A034
Multispeed 14 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A035
Multispeed 15 setting 0.0 or “start frequenc
” to “n-th maximum frequenc
”(Hz)
0.00
{ {
A038
Jog frequency setting "Start frequency" to 9.99 (Hz)
1.00
{ {
A039 Jog stop mode
00 (free-running after jogging stops [disabled during operation]),
01 (deceleration and stop after jogging stops [disabled during
operation]),
02 (DC braking after jogging stops [disabled during operation]),
03 (free-running after jogging stops [enabled during operation]),
04 (deceleration and stop after jogging stops [enabled during
operation]),
05
00
¯ {
*1 This setting is valid only when the OPE-SR is connected.