Chapter 4 List of Data Settings
4 - 6
Code Function name Monitored data or setting
Default
Setting
during
operation
(allowed
or not
)
Change
during
operation
(allowed
or not
)
_FF
AVR
A081 AVR function select 00
(
alwa
y
s on
)
, 01
(
alwa
y
s off
)
, 02
(
off durin
g
deceleration
)
02 ¯ ¯
A082 AVR voltage select
200 V class: 200, 215, 220, 230, 240 (V)
400 V class: 380, 400, 415, 440, 460, 480
(
V
)
200/400 ¯ ¯
Operation mode and acceleration/deceleration function
A085 Operation mode selection 00
(
normal operation
)
, 01
(
ener
gy
-savin
g
operation
)
00 ¯ ¯
A086 Ener
gy
savin
g
mode tunin
g
0.1 to 100.0 50.0 { {
A092 Acceleration
(
2
)
time settin
g
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600.
(
s
)
15.00 { {
A292 Acceleration
(
2
)
time settin
g
, 2nd moto
r
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600.
(
s
)
15.00 { {
A392 Acceleration
(
2
)
time settin
g
, 3rd moto
r
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600.
(
s
)
15.00 { {
A093 Deceleration
(
2
)
time settin
g
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600.
(
s
)
15.00 { {
A293 Deceleration
(
2
)
time settin
g
, 2nd moto
r
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600.
(
s
)
15.00 { {
A393 Deceleration
(
2
)
time settin
g
, 3rd moto
r
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600.
(
s
)
15.00 { {
A094
Select method to switch to Acc2/Dec2
profile
00 (switching by 2CH terminal), 01 (switching by setting),
02
(
switchin
g
onl
y
when rotation is reversed
)
00 ¯ ¯
A294
Select method to switch to Acc2/Dec2,
2nd moto
r
00 (switching by 2CH terminal), 01 (switching by setting),
02
(
switchin
g
onl
y
when rotation is reversed
)
00 ¯ ¯
A095 Acc1 to Acc2 fre
q
uenc
y
transition
p
oint 0.00 to 99.99, 100.0 to 400.0
(
Hz
)
0.00 ¯ ¯
A295
Acc1 to Acc2 frequency transition point,
2nd moto
r
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ ¯
A096 Dec1 to Dec2 frequenc
y
transition point 0.00 to 99.99, 100.0 to 400.0
(
Hz
)
0.00 ¯ ¯
A296
Dec1 to Dec2 frequency transition point,
2nd moto
r
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ ¯
A097 Acceleration curve selection
00 (linear), 01 (S curve), 02 (U curve),
03
(
inverted-U cur
v
e
)
, 04
(
EL-S curve
)
00 ¯ ¯
A098 Deceleration curve setting
00 (linear), 01 (S curve), 02 (U curve),
03
(
inverted-U curve
)
, 04
(
EL-S curve
)
00 ¯ ¯
External frequency adjustment
A101
[OI]-[L] input active range start
frequenc
y
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ {
A102
[OI]-[L] input active range end
frequenc
y
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ {
A103
[
OI
]
-
[
L
]
in
p
ut active ran
g
e start current 0. to "
[
OI
]
-
[
L
]
in
p
ut active ran
g
e end current"
(
%
)
20. ¯ {
A104 [OI]-[L] input active ran
g
e end current "[OI]-[L] input active ran
g
e start current" to 100.
(
%
)
100. ¯ {
A105
[
OI
]
-
[
L
]
in
p
ut start fre
q
uenc
y
enable 00
(
external start fre
q
uenc
y)
, 01
(
0 Hz
)
00 ¯ {
A111
[O2]-[L] input active range start
fre
q
uenc
y
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ {
A112
[O2]-[L] input active range end
frequenc
y
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ {
A113 [O2]-[L] input active ran
g
e start volta
g
e -100. to 02 end-frequenc
y
rate
(
%
)
-100. ¯ {
A114 [O2]-[L] input active ran
g
e end volta
g
e "02 start-frequenc
y
rate" to 100.
(
%
)
100. ¯ {
eratio
n and
decele
A131 Acceleration curve constants settin
g
01
(
smallest swellin
g)
to 10
(
lar
g
est swellin
g)
02 ¯ {
A132 Deceleration curve constants settin
g
01
(
smallest swellin
g)
to 10
(
lar
g
est swellin
g)
02 ¯ {
Operation-target frequency
A141 Operation-target frequency selection 1
00 (digital operator), 01 (keypad potentiometer),
02 (input via O), 03 (input via OI),
04 (external communication), 05 (option 1), 06 (option 2),
07
(
pulse-strin
g
frequenc
y
input
)
02 ¯ {
A142 Operation-target frequency selection 2
00 (digital operator), 01 (keypad potentiometer), 02 (input
via O), 03 (input via OI), 04 (external communication), 05
(
option 1
)
, 06
(
option 2
)
, 07
(
pulse-strin
g
frequenc
y
input
)
03 ¯ {
A143 Operator selection
00 (addition: A141 + A142), 01 (subtraction: A141 - A142),
02
(
multiplication: A141 x A142
)
00 ¯ {
A145 Frequenc
y
to be added 0.00 to 99.99, 100.0 to 400.0
(
Hz
)
0.00 ¯ {
A146 Sign of the frequency to be added
00 (frequency command + A145),
01
(
frequenc
y
command - A145
)
00 ¯ {
Acceleration and
deceleration
A150
EL-S-curve acceleration
ratio 1
0. to 50. (%) 25. ¯ ¯
A151
EL-S-curve acceleration
ratio 2
0. to 50. (%) 25. ¯ ¯
A152
EL-S-cu
r
ve deceleration
ratio 1
0. to 50. (%) 25. ¯ ¯
A153
EL-S-curve deceleration
ratio 2
0. to 50. (%) 25. ¯ ¯
*1 This setting is valid only when the OPE-SR is connected.