Chapter 4 List of Data Settings
4 - 14
Code Function name Monitored data or setting
Default
Setting
during
operation
(allowed
or not
Change
during
operation
(allowed
or not
_FF
Control constants
H001 Auto-tuning Setting
00 (disabling auto-tuning),
01 (auto-tuning without rotation),
02
00 ¯ ¯
H002 Motor data selection, 1st motor
00 (Hitachi standard data), 01 (auto-tuned data),
02
auto-tuned data [with online auto-tunin
00 ¯ ¯
H202 Motor data selection, 2nd motor
00 (Hitachi standard data), 01 (auto-tuned data),
02
auto-tuned data [with online auto-tunin
4 ¯ ¯
H204 Motor poles settin
0.001 to 9.999, 10.00 to 80.00
1.590 { {
H205 Motor speed constant, 2nd moto
0.001 to 9.999, 10.00 to 80.00
1.590 { {
H006 Motor stabilization constant, 1st moto
0. to 255. 100. { {
H206 Motor stabilization constant, 2nd moto
0. to 255. 100. { {
H306 Motor stabilization constant, 3rd moto
0. to 255. 100. { {
H020 Motor constant R1, 1st motor 0.001 to 9.999, 10.00 to 65.53 (Ω)
Depending on
motor capacit
¯ ¯
H220 Motor constant R1, 2nd motor 0.001 to 9.999, 10.00 to 65.53 (Ω)
Depending on
motor capacit
¯ ¯
H021 Motor constant R2, 1st motor 0.001 to 9.999, 10.00 to 65.53 (Ω)
Depending on
motor capacit
¯ ¯
H221 Motor constant R2, 2nd motor 0.001 to 9.999, 10.00 to 65.53 (Ω)
Depending on
motor capacit
¯ ¯
H022 Motor constant L, 1st motor 0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on
motor ca
¯ ¯
H222 Motor constant L, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on
motor ca
¯ ¯
H023 Motor constant Io 0.01 to 99.99, 100.0 to 655.3 (A)
Depending on
motor capacit
¯ ¯
H223 Motor constant Io, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (A)
Depending on
motor capacit
¯ ¯
H024 Motor constant J
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9,
1000. to 9999.
Depending on
motor capacit
¯ ¯
H224 Motor constant J, 2nd motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9,
1000. to 9999.
Depending on
motor capacit
¯ ¯
H030 Auto constant R1, 1st motor 0.001 to 9.999, 10.00 to 65.53 (Ω)
Depending on
motor ca
¯ ¯
H230 Auto constant R1, 2nd motor 0.001 to 9.999, 10.00 to 65.53 (Ω)
Depending on
motor ca
¯ ¯
H031 Auto constant R2, 1st motor 0.001 to 9.999, 10.00 to 65.53 (Ω)
Depending on
motor capacit
¯ ¯
H231 Auto constant R2, 2nd motor 0.001 to 9.999, 10.00 to 65.53 (Ω)
Depending on
motor capacit
¯ ¯
H032 Auto constant L, 1st motor 0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on
motor capacit
¯ ¯
H232 Auto constant L, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on
motor capacit
¯ ¯
H033 Auto constant Io, 1st motor 0.01 to 99.99, 100.0 to 655.3 (A)
Depending on
motor ca
¯ ¯
H233 Auto constant Io, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (A)
Depending on
motor ca
¯ ¯
H034 Auto constant J, 1st motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9,
1000. to 9999.
Depending on
motor capacit
¯ ¯
H234 Auto constant J, 2nd motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9,
1000. to 9999.
Depending on
motor capacit
0.0 to 999.9, 1000. 100.0 { {
H250 PI proportional
0.0 to 999.9, 1000. 100.0 { {
H051 PI inte
0.0 to 999.9, 1000. 100.0 { {
H251 PI inte
0.0 to 999.9, 1000. 100.0 { {
H052
P proportional gain setting for
1st moto
0.01 to 10.00 1.00 { {
H252
P proportional gain setting for
2nd moto
0.01 to 10.00 1.00 { {
H070
Terminal selection PI proportional gain
settin
0.0 to 999.9, 1000. 100.0 { {
H071
Terminal selection PI integral gain
settin
0.0 to 999.9, 1000. 100.0 { {
H072
Terminal selection P proportional gain
settin
0.00 to 10.00 1.00 { {
H073 Gain switchin
100. { {
(Note)<>indicate the setting range of 90 to 160kW