6 Building air conditioning controls
CSNET Manager LT/XT
TCGB0106 rev.0 - 12/2014
557557
6
Address
(Note 1)
Name Description Read/Write
6 SET_TSET
Setting temperature
17ºC ~ 30ºC
Read/Write
7 SET_LOUVER
Louver setting
0 ~ 8 (8 is Auto)
Read/Write
8 SET_CENTRAL
Central Setting:
Bit 0: ON/OFF (always can be stopped)
Bit 1: Mode
Bit 2: Setting temperature
Bit 3: Fan
Read/Write
9 READ_ONOFF
ON/OFF read:
0: OFF
1: ON
Read
10 READ_MODE
Mode read:
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Read
11 READ_FAN
Fan read
0: Low
1: Medium
2: High
Read
12 READ_TSET
Setting temperature read
(17ºC to 30ºC)
Read
13 READ_LOUVER
Louver read
0 ~ 8 (8 is Auto)
Read
14 RCS_GROUP
Remote controller group
0 ~ 255
Read
15 TIN Inlet temperature (Note 2) Read
16 TOUT Outlet temperature (Note 2) Read
17 TGAS Gas pipe temperature (Note 2) Read
18 TLIQUID Liquid pipe temperature (Note 2) Read
19 ERROR_CODE Alarm code Read
20 STOP_CAUSE Compressor stop cause Read
21 VALVE_OPEN Indoor unit expansion valve opening Read
22 OPER_CONDITION
Unit operation condition
0: OFF
1: Thermo OFF
2: Thermo ON
3: Alarm
Read
23 DEFROST Defrost Read
24 AMBIENT_TEMP Ambient temperature (Note 2) Read
25 RCS_TEMP
Remote control switch temperature
(Only when available in unit) (Note 2)
Read
26 TIMER_DISABLED
Timer disabled
0: Disabled
1: Enabled
Read/Write
27 OPTIONS Options setting Read
28 POWER Calculated power consumption Read
29 COMP_QTY Running compressor quantity (Note 5) Read
30 COMP_FREQ Inverter compressor frequency Read
31 REM_TEMP
Remote sensor temperature
(Only when accessory is installed) (Note 2)
Read
1. Offset position is: 20000 + N*32 + Address as shown in table, where N is unit address. Unit address as set in CSNET Manager BMS
conguration dialogue. Be careful because we are using address 0 as rst register and in Mobdus could be used number 1 as rst value.
In that case, it will be necessary to add 1 to the address calculation.
2. These numbers refer to signed 16-bit value using 2-complement format for negative values.
3. In case that the installation will use more than one CSNET Manager, it will use different device Ids, using Virtual Ids. Refer to the
conguration of your BMS to Ethernet adapter to know how it works.
4. Register number 10 is used for general alarm status.
5. Running compressor quantity is only valid for units with more than one compressor.