EasyManua.ls Logo

Hitachi RAS-2WHVRP - Input terminals (Default input functions)

Hitachi RAS-2WHVRP
142 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Capacity and selection data
YUTAKI S COMBI
TCGB0123 rev.2 - 10/2019
61
3
3.2.2 Maximum cooling capacity table (kW)
Ambient temperature (ºC WB)
10 15 20 25 30 35 40 45
System
Water
outlet
temp
(ºC)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
RAS-2WHVRP+RWD-2.0NRW(S)
E-(200/260)S(-K)(-W)
22 7.40 0.95 7.80 6.93 1.03 6.74 6.45 1.11 5.83 5.98 1.19 5.04 5.50 1.26 4.35
18 7.50 0.96 7.80 7.10 0.97 7.30 6.80 1.08 6.30 6.40 1.21 5.30 5.75 1.27 4.54 5.10 1.32 3.85
15 7.00 0.97 7.20 6.92 0.99 7.02 6.83 1.00 6.84 6.75 1.01 6.67 6.27 1.10 5.68 5.79 1.19 4.84 5.31 1.29 4.13 4.83 1.38 3.50
10 6.80 0.97 7.00 6.58 1.01 6.54 6.37 1.04 6.12 6.15 1.08 5.72 5.71 1.17 4.86 5.26 1.27 4.14 4.82 1.37 3.52 4.37 1.47 2.98
7 6.20 0.98 6.30 6.10 1.03 5.94 6.00 1.07 5.60 5.80 1.12 5.20 5.40 1.23 4.40 5.00 1.33 3.75 4.55 1.43 3.19 4.10 1.52 2.70
5 5.50 1.08 5.10 5.20 1.17 4.46 4.90 1.26 3.90 4.60 1.34 3.42 4.30 1.43 3.00 4.00 1.52 2.63 3.70 1.61 2.30
RAS-2.5WHVRP+RWD-
2.5NRW(S)E-(200/260)S(-K)(-W)
22 8.70 1.19 7.30 8.10 1.27 6.38 7.50 1.35 5.57 6.90 1.42 4.85 6.30 1.50 4.20
18 8.50 1.21 7.00 8.30 1.24 6.70 7.90 1.36 5.80 7.20 1.48 4.85 6.60 1.58 4.19 6.00 1.67 3.60
15 8.10 1.25 6.50 8.03 1.26 6.39 7.96 1.27 6.28 7.89 1.28 6.17 7.35 1.39 5.29 6.81 1.50 4.54 6.27 1.61 3.90 5.73 1.72 3.34
10 7.60 1.25 6.10 7.47 1.28 5.84 7.34 1.31 5.59 7.21 1.35 5.35 6.73 1.46 4.60 6.24 1.57 3.96 5.76 1.69 3.41 5.27 1.80 2.93
7 7.10 1.31 5.40 7.00 1.34 5.23 6.90 1.36 5.06 6.80 1.39 4.90 6.30 1.58 4.00 6.00 1.74 3.45 5.50 1.80 3.06 5.00 1.85 2.70
5 6.80 1.36 5.00 6.43 1.49 4.32 6.07 1.62 3.75 5.70 1.75 3.26 5.33 1.88 2.84 4.97 2.01 2.47 4.60 2.14 2.15
RAS-3WHVRP+RWD-3.0NRW(S)
E-(200/260)S(-K)(-W)
22 10.50 1.67 6.30 9.90 1.73 5.72 9.30 1.80 5.17 8.70 1.86 4.67 8.10 1.93 4.20
18 10.60 1.64 6.45 10.20 1.71 5.95 9.50 1.84 5.15 9.00 1.94 4.65 8.00 1.98 4.04 7.00 2.03 3.45
15 9.50 1.40 6.80 9.52 1.52 6.26 9.55 1.65 5.80 9.57 1.77 5.40 8.86 1.87 4.75 8.15 1.96 4.16 7.44 2.05 3.63 6.73 2.14 3.14
10 8.80 1.44 6.10 8.71 1.58 5.50 8.62 1.73 4.99 8.53 1.87 4.56 7.96 1.99 4.01 7.40 2.10 3.52 6.84 2.22 3.08 6.27 2.33 2.69
7 8.10 1.56 5.20 8.03 1.68 4.78 7.97 1.80 4.42 7.90 1.93 4.10 7.60 2.05 3.70 7.00 2.19 3.20 6.50 2.32 2.80 6.00 2.45 2.45
5 8.00 1.74 4.60 7.68 1.86 4.12 7.35 1.99 3.70 7.03 2.11 3.33 6.70 2.23 3.00 6.15 2.45 2.51 5.60 2.67 2.10
? NOTE
CAP: Capacity at compressor maximum frequency. Capacity is valid for difference between water inlet and water outlet of 3-8ºC.
IPT: Total input power.

Table of Contents

Other manuals for Hitachi RAS-2WHVRP

Related product manuals