4. Electrical wiring
101
SMGB0079 rev.0 - 01/2013
4
4.5 H-LINK II system
The H-LINK II is the wiring connection system between units.
The H-LINK II wiring system only needs:
Two transmission wires connecting each indoor and outdoor unit for a total of 64 refrigerant cycles.
Connection wiring for all indoor and outdoor units in series.
C A U T I O N
TheH-LINKIIsystemcannotbeappliedtothemodelswiththeoldcycle,nortounitswithanoldtransmission.
4.5.1  Features
The total wiring length is considerably reduced compared to traditional connections.
Only one connection is required for the wiring between the indoor and outdoor units.
The wiring connection of the complementary central control devices is easy.
N O T E
CSNETWEBisacentralizedcontrolsystemwhichallowstheinstallationtobecontrolledremotely.Itcanbe
connectedatanypointofthelocalcorporatenetwork,orevenviatheInternet.
4.5.2  Specications
A: outdoor unit.
B: indoor unit.
C: refrigerant cycle.
D: transmission cables.
E: refrigerant piping.
A refrigerant cycle
Outdoor unit
Indoor units
Transmission cables
Refrigerant piping
Cable features
Transmission cable: 2-wire.
Polarity of transmission cable: non-polar wire.
Maximum number of indoor units that can be connected: 4 units per cycle and 160 units per H-LINK II system.
Maximum wiring length: total 1000 m (including CSNET WEB).
It is possible to increase the maximum wiring length up to 5000 m by using up to four PSC-5HR units.
Recommended cable: shielded twisted pair cable, over 0.75 mm
2
(Equivalent to KPEV-S).
Voltage: 5V DC.
C A U T I O N
FortheH-LINKIIsystemitmustbeusedtwistedshieldedpaircableorshieldedpaircable.