5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
126
5.2.2 Description of the optional remote control functions (PC-ARFP1E)
b1 – Removal of heating temperature compensation
This function is used to adjust the dierence of temperature between the setting temperature of the remote control switch
and the inlet air temperature of the indoor unit.
This is useful when the inlet air thermistor is not placed inside the indoor unit or due to uneven Heat Load or for example
in standard heating mode, the suction air temperature is greater than that of the room, therefore the setting temperature
used according to the factory setting is calibrated to the indicated temperature +4 °C, but depending on the room
conditions can be necessary to compensate a smaller value.
b2 – Circulator function at heating Thermo-OFF
This function means that the fan unit remains running after the air conditioning system has stopped in heating mode to
prevent the air in the room from stratifying.
This function is useful when the air in the room is stratied (hot air accumulates at the ceiling). Air stratication may occur
if has been selected fan speed changes to LOW when the thermostat of the unit is stopped. This function prevents air
stratication in the room after stopping the air conditioning system.
This function maintains the fan speed, whether the thermostat is on or o. Hence, the air movement in the room is kept
at the same level to ensure even air distribution.
? NOTE
• If the indoor unit has an automatic louver, this function also remains active when the heating thermostat is switched o.
• Everyone has a dierent perception of coolness, heat and air ow and, therefore, this issue should be discussed with the client and
the unit set according to the results of the conversation.
b3 – Forced compressor operation for at least three minutes
This function is used to allow the setting of C7 (Cancellation of the forced compressor operation for at least 3 minutes)
preventing it from being started or stopped the compressor for periods of less than 3 minutes.
? NOTE
• In the case of SET FREE units, forced compressor operation for at least 3 minutes is standard, even when the setting is not available.
• The compressor stops immediately when the safety device is activated or ON/OFF is pressed.
• To cancel this function, see C7 – Cancellation of the forced compressor operation for at least three minutes.
• When this function is cancelled, the mode enabling operations for a minimum of 3 minutes remains available.
b4 – Change the lter cleaning period
This function is used to modify the period during which the remote control indicates the air lter replacement. The lter
cleaning period can be changed depending on the condition of the lter.
? NOTE
• The remaining number of hours before cleaning the lter is factory-set for all indoor unit models b2=02 (1200 hours).
• For RPK-FSR(H)M models Factory-Setting is b4=00: Standard setting 200 hrs.
b5 – Locking of operation mode
This function is used when the operating mode does not have to be changed. Once the unit operating mode has been
selected, this function prevents it from being modied from the remote control.
b6 – Locking of setting temperature
This function is used when the temperature setting does not have to be changed. Once the unit temperature has been
selected, this function prevents it from being modied from the remote control.
b7 – Setting operation mode as cooling only
This function is available to use refrigeration mode only and to prevent heating mode from being enabled. When this
function is selected, heating operation and the automatic COOL/HEAT operation are cancelled.