EasyManua.ls Logo

Hitachi RCIM-1.5FSRE - Removal Of The Float Switch; Removal Of The Drain Mechanism; Removal Of The Drain Pan

Hitachi RCIM-1.5FSRE
314 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Servicing
RCD-(0.8-6.0)FSR - 2-way cassette
SMGB0137 rev.0 - 05/2021
207
7
7.3.6 Removal of the oat switch
1 Remove the Drain pan, as explained in “7.3.8 Removal
of the drain pan”
2 Remove the lead wires for the Drain up mechanism, the 
Float switch and the Outlet air thermistor, as explained 
in “7.3.6 Removal of the oat switch”
3 Remove the Float switch lead wire from the core clamp 
at the evaporator partition plate.
4 Cut the plastic cord bands gathering the lead wires of 
the Float switch, the drain mechanism and the Outlet air 
thermistor.
5 Remove the Float switch by removing the xing screws 
of the Float switch xing plate and remove the Float 
switch.
? NOTE
for the reassembling, proceed in the reverse way than
disassembling.
The torque value of the resin nut is 0.3 - 0.4 Nm. If the torque
value is higher, the nut will be damaged.
Float switch
Evaporator
partition plate
Code clamp
Outlet air thermistor
Drain-up mechanism
Screw
Plastic cord band
7.3.7 Removal of the drain mechanism
1 Remove the drain pan according to the item “7.1.6
Removing drain pan”.
2 Remove the drain-up mechanism lead wire from the 
code clamp attached to the evaporator partition plate.
3 Cut the clamping band gathering the lead wires 
for drain-up mechanism, oat switch and outlet air 
thermistor.
4 Spread out the plastic band for drain hose the remove 
the drain hose from drain-up mechanism.
5 Remove three xing screws for the drain-up 
mechanism. Make sure to hold the drain-up mechanism 
by hand so that it will not fall o󰀨.
6 Then remove the drain-up mechanism.
Float switch
Evaporator
partition plate
Code clamp
Outlet air thermistor
Drain-up mechanism
Screw
Plastic cord band
7.3.8 Removal of the drain pan
1 Remove the air panel according to the item “7.1.4 Removing turbo fan and fan motor”.
2 Remove the screw then remove the wire cover.
3 Remove the electrical box cover according to the item “7.1.2 Removing electrical box cover”.
Disconnect the connectors of the gas pipe thermistor, the liquid pipe thermistor, the expansion valve and the fan 
motor.
4 Remove the bell-mouth according to the item “7.1.4 Removing turbo fan and fan motor”.
5 Draining:
a. Pull out the rubber plug from the drain pan, and drain the water remaining in the drain pan. Although silicon 
sealant is applied over the rubber plug, the rubber plug can be removed by pulling the bottom side.
? NOTE
Be careful not to damage the rubber plug with a cutter knife.
b.  Check any clogging in the drain hole.